MAIN OVERVIEW FEATURES: Input Receptacles: 2 x IEC 60320 C20Output Receptacles: 2 x IEC 60320 C19,8 x IEC 60320 C13Input Voltage: 230 V ACInput Voltage Range: 200 V AC - 240 V ACOutput Voltage: 200 V AC,208 V AC,220 V AC,230 V AC,240 V ACPlacement: RackRack Height: 1UHeight: 1.7"Width: 17.3"Depth: 14"Weight (Approximate): 10.30 lbPackage Contents: Metered PDUMH20HVAT 10-Outlets PDUUser Manual with Warranty InformationEnvironmentally Friendly: YesEnvironmental Certification: RoHSLimited Warranty: 2 Year
Learn more about the Tripp Lite PDUMH20HVAT
Model
Brand
Tripp Lite
Model
PDUMH20HVAT
Details
Type
Switched, Metered
Rack Size
1U
Style
Horizontal
Front Panel LEDs
8 front panel LEDs display power on - off status for each C13 outlet, plus 2 LEDs for power status on Primary and Secondary input connection. Digital current meter display shows the amount of power consumption in amps for entire PDU output.
Certifications
Tested to UL 60950 (USA, Canada), CE (Europe), Class A (Emissions), NOM (Mexico), RoHS Complaint
ROHS
Yes
Input
Input Voltage
200 V AC Single-phase 208 V AC Single-phase 230 V AC Single-phase 240 V AC Single-phase
Maximum Input Current
20A
Input Connector(s)
IEC-320 C20
Cord Length
Includes two 12 Feet C19 to C20 cables
Output
Output Voltage
200V, 208V, 220V, 230V, 240V
Output Frequency
50/60Hz
Output Connector(s)
8 x IEC-C13, 2 x IEC-C19
Environmental
Operating Relative Humidity
5 - 95%
Operating Elevation
0 - 10000 Feet
Storage Temperature
-15 - 50 Celcius degree
Feature
Features
200 - 240V 16A Automatic Transfer Switch (ATS) / Metered PDU (Power Distribution unit)
Provides a redundant power option for critical networking equipment with a single input power cord
2 digit display reports output power consumption in amps
Set of two C20 inlets support connection to separate PRIMARY and SECONDARY power sources
ATS circuits normally maintain output sourced from the primary input cable; As primary input power fails or becomes unstable, the ATS will switch to maintain output sourced from the secondary input cable until power on the primary input is restored and stable
ATS configurations enable fault-tolerant, hot-swappable UPS protection when used with a single UPS and fully redundant UPS protection when each cord is connected to a separate UPS system (in a two-UPS environment, the primary input cable must be supported by an online UPS with zero transfer time similar to Tripp Lite SmartOnline series)
Advanced ATS configurations utilizing separate mains circuits, backup generators and even separate out of phase utility power grid feeds are fully supported
On-board ATS processor constantly evaluates power quality on both inputs to prevent transfer to the secondary source when unavailable or of lower quality than the primary source
Super-fast switchover between primary and secondary power sources occurs in 2-5 milliseconds
Built-in card slot supports optional SNMPWEBCARD for permanent upgrade to a switched & monitored PDU system
Outlets are factory programmed for sequential turn-on at 250 milliscond intervals when the PDU is first energized to prevent inrush-related equipment interaction on startup
Front panel LEDs confirm power availability on both input lines
Dimensions & Weight
Dimensions
1.70" x 17.30" x 14.00"
Weight
10.30 lbs.
Details
Package Includes
Metered PDU with ATS Support User manual with warranty information